RSCAC-1333 Series (9″H, 60A Main Bkr, 22kAIC, 12x load-bkr positions, Strikesorb)
AC Disconnect with Integrated Surge Protection for Small Cell Radio Heads
Suitable for Use as Service Equipment (SUSE) without condition with 60A main breaker
Features
- 60A main breaker Suitable for Use as Service Equipment (SUSE) without condition per UL and NEC
- 22kA Fault Current Rating (kAIC), but can be configured with 42kAIC main breaker
- Up to six 15A, 20A or 30A duplex branch breakers providing (12) 120VAC circuits which can be bridged to provide 240V
- 120/240VAC split-phase configuration or 2 of 3 phases in a 208/120VAC 3-phase configuration
- Employs the Strikesorb 30-A-2CHV Surge Protective Device (SPD)
- The Strikesorb 30-A-2CHV is a Class I SPD, certified by VDE per the IEC 61643 11 standard as suitable for installation in areas where induced lightning exposure is expected
- Strikesorb 30-A-2CHV is able to withstand direct surge currents up to 5kA (10/350 μs) and induced surge currents of up to 60kA (8/20)
- Provides low let through / clamping voltage – as it does not employ spark gaps or other switching elements
- Strikesorb offers unique protection levels for wireless and small cell applications
- Comes with two compression fittings that can be replaced with 1.5″ NPT conduit fittings
- Provided Line1-to-Neutral and Line2-to-Neutral protection for 120/240VAC split-phase systems. Can also protect Ph1-to-Neutral and Ph2-to-Neutral (2 out of 3 phases) for 208/120VAC 3-Phase systems
- Compatible with duplex/double pole breakers
- Patent pending design
- Pole mount bracket facilitates mounting up to 4″ diameter pole using existing clamps. Can also be banded to any diameter pole. Center mount holes (5/8″) for center pole mount
Benefits
- Offers unique maintenance free protection
- NEMA 4X or IP 68 & NEMA 6/6P rated enclosure, allowing for installation in harsh environments Utilizes a IP68/NEMA 6/6P rated enclosure, allowing for indoor or outdoor installation
- Lightweight design allows easy installation